Search on site:  
 
 

topMaintenance Notes

  • Faulty or Under warrany TDK power module return procedure .edms.(DELTA)

topDesign Notes

  • (2021-11-xx) TDK commercial modules new reference :
    • Yves + Michel
      • New reference TDK GSP10-1000-3P400 [1kA;10V] 2U replacing old one [3U]
        - This new reference is the standard one from 2021.
        - It requires a new rack layout since the modules are 2U height (instead of 3U).
        - These modules are much better regarding the current sharing when operating in parallel (no need of extra cern card).
        - The new reference shows almost same voltage bandwidth than old ones (150 Hz); some tests (using fresco) indicates a high precision current source (20mA of error over 2 kA) with 120 Hz of bandwidth in current.
        - Discussion with TDK indicates that <50V output module can handle up to 800V output common mode voltage.