Design Notes
- (2020-03-04) Informal discussion:
- Serge + Nicolas: AC departure for 18kA
- HL-LHC[18kA; +-10V] converter requires 170A departure, not 32A as stated in functional specification
- Serge said he could use the two 140A departures already present for old IT system
- Nicolas will check if the departure could be upgraded
- (2020-02-10) Meeting:
- Olivier F. + Edwin + Nicolas: Racks needed for HPM
- Two news racks will be provided by HPM for both HL-LHC converter (featuring air conditioning)
- A third rack is needed for the actual LHC13kA;08V and RPTE converter
- A fourth rack will be shared with LPC (interlock) and HPM for potential future use (computer...)
|