Search on site:  
 
 
  •  

topOverview

This pages describes the tests which are done to ensure a commercial power source is controllable by a FGC controller, evaluating its performances.

An EDMS doc: MANUFACTURER REFERENCE CERN Controllability Evaluation is created, with 2 EDMS sub-doc:
  • EDMS doc: MANUFACTURER REF CERN Single Config FGC-Controlled Evaluation with a report file.
  • EDMS doc: MANUFACTURER REF CERN Parrallel Config FGC-Controlled Evaluation with a report file.

topPoints of interest / compatibility

  • Performances of the Power Source, being driven by a FGC, as a current source
    • Single or Parrallel power module configuration.
    • Commerical Power Source is integrated in a standard EPC Power Converter, with the addition of a FGC controller and a DCCT measurement.
    • Different sequences types (static, dynamic references) are tested, using EPC tools (spy, fgcrun+) to check the performance obtained are correct, with a great focus on the current control.
    • Tests are performed with different current loop settings, and acquiring output current, on different loads (R, R+L, L), to deduce the voltage source performance and integrity.