Point Location Radiation
Status
HEH
Fluence / Yr
LHC60A-08V LHC120A-10V LHC600A-10V LHC600A-40V LHC4-6-8kA-08V LHC13kA-18V Location Sum Fault / Location Relative Fault
[%]
Save (yves thurel only)
[ .. ] 752 Units 290 Units 400 Units 37 Units 189 Units 16 Units
                         
X Tunnel Unsafe (Cell 12 to 16) 2.00E+09 192           Tunnel 17 40  %
X Tunnel Unsafe (Cell 18 to 34) 7.00E+08 560           Tunnel 18 41  %
1 RR13 Unsafe 1.50E+08   18 14   15   RR13 2 4  %
1 RR17 Unsafe 1.50E+08   18 14   15   RR17 2 4  %
1 UL14 Relocation > Unsafe 6.00E+06   5 8   2   UL14 0 0  %
1 UL16 Relocation > Unsafe 6.00E+06   5 8   2   UL16 0 0  %
1 USA15 Safe 1.00E+05         1   USA15 0 0  %
2 UA23 Safe 1.00E+05   16 24   16 2 UA23 0 0  %
2 UA23-Maze Unsafe 2.00E+06   5 7   2   UA23-Maze 0 0  %
2 UJ23 Safe 9.00E+05   8         UJ23 0 0  %
2 UA27 Safe 1.00E+05   24 24   16 2 UA27 0 0  %
2 UA27-Maze Unsafe 2.00E+06   5 7   2   UA27-Maze 0 0  %
3 UJ33 Safe 1.00E+05   10 46 24     UJ33 0 0  %
4 UA43 Safe 1.00E+05   6 24   14 2 UA43 0 0  %
4 UJ43 Safe 1.00E+05   8         UJ43 0 0  %
4 UA47 Safe 1.00E+05   6 24   14 2 UA47 0 0  %
4 UJ47 Safe 1.00E+05   8         UJ47 0 0  %
5 RR53 Shielding > Unsafe 9.80E+07   18 14   15   RR53 1 2  %
5 RR57 Shielding > Unsafe 9.80E+07   18 14   15   RR57 1 2  %
5 UL557 Relocation > Safe 1.00E+05   5 8   2   UL557 0 0  %
5 USC55 Safe 1.00E+05   5 8   2   USC55 0 0  %
6 UA63 Safe 1.00E+05   12 23   4 2 UA63 0 0  %
6 UJ63 Safe 1.00E+05         6   UJ63 0 0  %
6 UA67 Safe 1.00E+05   12 23   4 2 UA67 0 0  %
6 UJ67 Safe 1.00E+05         6   UJ67 0 0  %
7 TZ76 Relocation > Safe 1.00E+05       12     TZ76 0 0  %
7 RR73 Unsafe 1.60E+08   10 24       RR73 1 3  %
7 RR77 Unsafe 1.60E+08   10 24       RR77 1 3  %
8 UA83 Safe 1.00E+05   16 24 1 16 2 UA83 0 0  %
8 UA83-Maze Unsafe 2.00E+06   5 7   2   UA83-Maze 0 0  %
8 UJ83 Safe 1.00E+05   8         UJ83 0 0  %
8 UA87 Safe 1.00E+05   16 24   16 2 UA87 0 0  %
8 UA87-Maze Unsafe 2.00E+06   5 7   2   UA87-Maze 0 0  %
8 UJ87 Safe 2.30E+06   8        
UJ87
0 0  %
FGC-only Cross Section è 4E-11 4E-11 4E-11 4E-11 4E-11 4E-11
Power Part Cross Section è 5.07E-12 1.72E-10 1.8E-10 1.17391E-09 1.73913E-10 2.6087E-07 Choose the adequate converter cross section (scenario)
Converter Cross Section è 4.51E-11 2.12E-10 2.20E-10 1.21E-09 2.14E-10 2.61E-07
Nb Events / Converter per Year (in Period of Interest) è 35.0 2.6 3.3 0.0 1.6 0.4 i.e. 42.9 events in total
Nb Events / FGC-only per Year (in Period of Interest) è 31.0 0.5 0.6 0.0 0.3 0.0 i.e. 32.4 events in total on FGC side only
Nb Events / Power-part only per Year (in Period of Interest) è 3.9 2.1 2.7 0.0 1.3 0.4 i.e. 10.4 events in total on power part only
Overall fluence received by irradiated units per year (all units) è 7.76E+11 1.23E+10 1.48E+10 3.70E+06 7.49E+09 1.60E+06
Date / Period of Interest è
2011 2012
LS1 2015
2016..2018 LS2 2020..2022 LS3 2024..2035 (HL-LHC)
 
      Clic on period of interest: 2016 .. 2018
Nb Total of SE Events
for EPC for Year considered
(see Fluence per point used > LHC operation)
43  Events/year during: 2016 .. 2018
last update 29-Jan-2016
FGC Cross Section 1.00E-12 Realistic (Measured, deduced, or if unknown the worst theoritically possible/2.3)
4.00E-11 Pessimistic (Worst theorically possible*)
FGClite Cross Section 3.00E-12 Realistic (Measured, deduced, or if unknown the worst theoritically possible/2.3)
3.00E-12 Pessimistic (Worst theorically possible*)
LHC60A-08V Cross Section 2.20E-12 Realistic (Measured, deduced, or if unknown the worst theoritically possible/2.3)
5.07E-12 Pessimistic (Worst theorically possible, based on 2012+2015 fluence with no event*)
LHC120A-10V Cross Section 7.48E-11 Realistic (Measured, deduced, or if unknown the worst theoritically possible/2.3)
2.40E-09 CPLD issue not solved
1.72E-10 Pessimistic (Worst theorically possible, based on 2012+2015 fluence with no event*)
LHC600A-10V Cross Section 7.83E-11 Realistic (Measured, deduced, or if unknown the worst theoritically possible/2.3)
1.80E-09 ACDC crash not solved
1.80E-10 Pessimistic (Worst theorically possible*)
LHC600A-40V Cross Section 1.17E-09 Realistic (Measured, deduced, or if unknown the worst theoritically possible/2.3)
2.70E-09 Pessimistic (Worst theorically possible*)
LHC4-6-8kA-08V Cross Section 1.74E-10 Realistic (Measured, deduced, or if unknown the worst theoritically possible/2.3)
4.00E-10 Pessimistic (Worst theorically possible*)
LHC13kA-18V Cross Section 2.61E-07 Realistic (Measured, deduced, or if unknown the worst theoritically possible/2.3)
6.00E-07 Pessimistic (Worst theorically possible*)
The worst theoritical cross section is obtained using or the worst cross section from radiation qualification test, or getting one event in past years (taking into account the highest radiation levels observed). This event correspond to the limit of detection. Example, it is possible to get 0 event in 2011, when the average value should have obtain is 1. Then cross section is set so that 2 events are calculated, even if not observed (low statistics)