Batiment 287-02 Test Bed 03.1_2 Load Inductive test load: 24mH 76mOhms (+ water load in series) Unit Serial Module Rack Unit Serial Rack NA Apparatus oscilloscope IAB and IAB FFT measured using SPY dedicated software (using FGC IAB 1kHz sampling signal). Result is given for info only, and is obtained from a low time constant load (to:0.3sec / fo:0.5Hz, with 55dB attenuation at 300Hz) To be put in perspective with a superconductive magnet giving very high time constant Loop settings are clbw,clbw2 3,15 Loop period is 1ms (10ms would create a lot of low frequency noise around 7Hz) V.meas is taken directly on rack top busbars with a oscilloscope running on battery