Date 2014-10-03 Batiment 287-02 Test Bed 03 Load Inductive test load: 13mH 30mOhms Unit Serial Module Rack (position 1.1) Unit Serial Rack NA Apparatus Oscilloscope on battery (TDS3014) + specific filter box (1kHz, 100kHz) Voltage is measured using filtering box for limiting antialiasing effect (FFT classical issue). 400 ms measurement : 1kHz 1st order box being used. 2 ms measurement : 100kHz 1st order box being used. (it means the noise at 100kHz is a bit reduced). Vout Ripple is measured bottom of the DC busbars (1.1), closest as possible from the Power Module. VE.Pos is measuring opening the top cover of the Power Module, meas points taken on the copper busbars at the input of the QLS stage. FGC (digital controller) is set in voltage mode to limit its effect (closing loop) in the measurement.