Batiment 287-02 Test Bed 02 Load Inductive test load: 13mH 30mOhms. Unit Serial Module Rack Prototype Unit Serial Rack NA Apparatus Spectrum Analyser Agilent 8594. Rack is powered through LISN, using 1.5m AC cable, 10cm above a copper ground without any direct connection to earth (only made through AC cable to LISN). EMC was tested with and without FGC rack to ensure no extra perturbation comes from it (mainly on AC side). Influence on the results was not significant. AC side was measured on all channels (3 phase + neutral). Measurement was done in all possible configurations (from 1 module only working in a rack whatever location possible up to a full Rack[4x] working at 100%).