Batiment 287-04 Test Bed 04.1 Load Inductive test load: (3mH-6mOhms) 250 mOhms (+ water load in series) Unit Serial Module Cobalt Rack Unit Serial Rack NA Apparatus oscilloscope + CERN Specific 10 kHz Low Pass Probe Method Earth system is disconnected, with output low polarity put to rack potential (CBN = earth). IAB and IAB FFT measured using SPY dedicated software (using FGC IAB 1kHz sampling signal). Result is given for info only, and is obtained from a low time constant load (to:0.3sec / fo:0.5Hz, with 55dB attenuation at 300Hz) To be put in perspective with a superconductive magnet giving very high time constant FGC3 Loop settings are clbw,clbw2,period_div 100,50,10 V.meas is taken directly on rack top busbars with a oscilloscope running on battery